46-7 - DIN
Flow and differential pressure regulator
USAGE
- Differential pressure and flow control
MEDIUM
						
							
								Water and other liquids
							
								Air and non-flammable gases
VERSION
						
							DIN
						
					
MEDIUM TEMPERATURE
						
							2
							to 150 °C /
							35.6
							to
							302 °F
						
					
VALVE SIZE
						
							
									DN 15
									to
									DN 50
PRESSURE RATING
						
							
									PN 16
									to
									PN 25
FUNCTION
- Differential pressure regulator
- Flow regulator
APPLICATION
- Valve closes when the differential pressure rises
- Valve closes when the flow rate rises
INSTALLATION
- Return flow pipe
FLOW RATE SET POINT
							
									0.01 to 15 m³/h / 0.04 to 66 US gal/min
								
						
FLOW RATE DP ACROSS RESTRICTION
							
									0.2 bar / 2.9 psi
								
						
DIFFERENTIAL PRESSURE SET POINT
							
									0.2 to 2 bar / 2.9 to 29.01 psi
								
						
Special features
- Flow and differential pressure regulator
- Consisting of valve with adjustable restriction and actuator with two diaphragms
- Single-seated valve with balanced plug
- Particularly suitable for district heating systems according to DIN 4747-1
- Internal overload protection in the actuator
Accessories
- - - -
Options
- - - -
Information
- T 3131 Type 46-7 and Type 47-5 Flow and Differential Pressure Regulators
 Type 47-1 Flow and Differential Pressure or Pressure Regulator
 [EN][DE]
- T 3095 Accessories · Differential pressure and flow regulators
 [EN][DE]
- T 3120 Information Sheet:
 Series 45, 46, 47 and 48 Self-operated Differential Pressure and Flow Regulators as well as Combined Reguators
 [EN][DE]
Support
Certificates
Only up-to-date documents are shown in the product selector. Check the documentation site for a list of all documents available.
Pin items on your list and contact us if you have any product-related questions.